Quick Compatibility Matrix
| Refrigerant | Oil Required | HCPro Oil | Vacuum Pump | Working Pressure |
|---|---|---|---|---|
| R-410A | POE (ISO VG 32) | RPO-32 | HCEC-6S 6 CFM | 800 PSI |
| R-32 (A2L) | POE (ISO VG 32) | RPO-32 | HCEC-6S 6 CFM | 800 PSI |
| R-454B (A2L) | POE (ISO VG 32) | RPO-32 | HCEC-6S 6 CFM | 800 PSI |
| R-134a (HVAC) | POE (ISO VG 32) | RPO-32 | HCEC-6S 6 CFM | 400 PSI |
| R-1234yf | POE-1234yf / PAG (auto) | RPO-32 (HVAC only) | HCEC-6S 6 CFM | 400 PSI |
| R-22 (retrofit only) | Mineral / POE (retrofit) | RPO-32 (retrofit) | HCEC-6S 6 CFM | 500 PSI |
| R-404A | POE (ISO VG 32) | RPO-32 | HCEC-6S 6 CFM | 800 PSI |
R-410A
R-410A is the dominant residential and light-commercial refrigerant in North America — being phased out by 2025 for new equipment under the EPA AIM Act. Operates at ~50% higher pressure than R-22, requiring POE oil and pressure-rated tools.
HCPro recommendation:
- Oil: RPO-32 POE
- Vacuum pump: HCEC-6S 6 CFM
- Adapter: Quick-Y vacuum adapter
- Burnout flush: Flash Flush
- Valve core service: Valve Core Removal Tool
R-32 (A2L)
R-32 is the leading A2L (mildly flammable, low-GWP) replacement for R-410A in mini-splits and residential heat pumps. Pressure profile is similar to R-410A but A2L handling protocols apply (no open flames near refrigerant, leak detection critical).
HCPro recommendation:
- Oil: RPO-32 POE
- Vacuum pump: HCEC-6S 6 CFM
- A2L-ready brass manifolds with 800 PSI working pressure
R-454B (A2L)
R-454B is the leading A2L replacement for R-410A in central residential AC and light commercial systems (Carrier, Lennox, Trane). Lower GWP than R-32. Similar handling requirements to R-32.
HCPro recommendation:
- Oil: RPO-32 POE
- Vacuum pump: HCEC-6S 6 CFM
- All A2L-ready HCPro tools and adapters
R-134a
R-134a is the standard for automotive A/C and some refrigeration systems. NEVER use POE in automotive A/C — most auto compressors require PAG. HVAC and refrigeration applications use POE.
HCPro recommendation (HVAC/refrigeration):
- Oil: RPO-32 POE
- Vacuum pump: HCEC-6S 6 CFM
R-1234yf
R-1234yf is the automotive A/C replacement for R-134a (lower GWP). Used in vehicles model year 2015+. Most automotive applications use POE-1234yf or PAG oil per OEM spec.
R-22 (Phased Out — Retrofit Only)
R-22 production ended January 2020 under the Clean Air Act. Service-only allowed using recovered or reclaimed stock. Most R-22 work today is retrofit to R-410A or R-32.
HCPro recommendation for R-22 retrofit:
- Flash Flush to clean mineral oil from the line set
- RPO-32 POE as the new system oil
- New TXV or service ports rated for the higher pressure
R-404A and Refrigeration Blends
R-404A is a refrigeration blend used in commercial freezers and low-temp refrigeration. Being phased out for low-GWP alternatives like R-448A and R-449A. POE oil compatible.
HCPro recommendation:
- Oil: RPO-32 POE
- Vacuum pump: HCEC-6S 6 CFM